Heat pumps low carbon

Hot water cylinders for heat pumps: sizing and legionella

How to size a heat pump cylinder, why coil area sets reheat time, and how to set a pasteurisation cycle that meets HSE temperature guidance.

Ava research teamPublished 7 min read

On this page
  1. The cylinder is where heat pump jobs go wrong
  2. Sizing: start from people and habits
  3. Where the cylinder goes
  4. Coil size and reheat time
  5. Legionella: what HSE guidance actually says
  6. Setting up the pasteurisation cycle
  7. Unvented rules and paperwork
  8. Handover checklist
  9. Frequently asked questions
  10. References

Key takeaways

  • Most homes in England run a combi boiler[1], so many heat pump jobs begin with finding space for a cylinder the customer never had.
  • Size from the household's habits and peak demand, not from the tank being removed.
  • Heat pumps heat water at lower flow temperatures, so coil surface area, not just volume, decides how fast the cylinder recovers.
  • HSE guidance is to store hot water at 60°C or above and reach 50°C at outlets within a minute[2]; a scheduled pasteurisation cycle closes the gap when the heat pump stores lower.
  • Write the cycle, the immersion wiring and the settings into the handover so nobody switches them off to save money.

The cylinder is where heat pump jobs go wrong

Customers judge a new heating system by two things: are the rooms warm, and does the shower run hot. The second is often decided by a cylinder choice made in a hurry at quote stage. In England, 63% of homes had a condensing combi boiler in 2024[1], and 55% of heat pump and biomass installations funded by the Boiler Upgrade Scheme replaced gas systems[3]. Put together, a large share of heat pump customers are moving from instant hot water to stored hot water for the first time.

That changes the conversation. You are not swapping like for like; you are asking someone to give up an airing cupboard or part of a bedroom, and to accept that hot water is a finite store that has to recover. Get the size, the coil and the controls right and they rarely think about it again.

Sizing: start from people and habits

  1. Count people and peak events

    Ask how many people live there now and in five years, and when the busiest half hour is: two showers back to back before school, or a bath every evening.

  2. Separate showers from baths

    A bath empties far more of the store in one go than a short shower. A household that bathes daily needs more stored volume than one that only showers.

  3. Check the shower type

    A mixer shower fed by an unvented cylinder can run at a much higher flow than the old gravity shower. Ask about flow expectations and any body jets or rainfall heads.

  4. Decide the storage temperature

    A cylinder stored at a lower temperature delivers less usable hot water than the same tank stored hotter, so the heat pump setting and the volume have to be chosen together.

  5. Check the space and the route

    Measure the cupboard, the door and the stairs. A taller, slimmer cylinder may fit where a squat one will not, but check the clearance for the discharge pipework and service access.

  6. Run the manufacturer's sizing tool

    Use your figures in the cylinder or heat pump manufacturer's tool and keep the output with the job file.

Example starting points only. Always confirm with the manufacturer's sizing tool and the customer's actual habits.
Household (Example)Typical patternStarting point to test
1 to 2 peopleShowers onlyAround 150 to 180 litres
3 peopleShowers, occasional bathAround 180 to 210 litres
4 peopleTwo morning showers and a bath most eveningsAround 250 litres
5 or more peopleOverlapping showers and bathsAround 300 litres, or check twin-cylinder options

Where the cylinder goes

Location affects performance as much as size. The ideal spot is inside the heated envelope, close to the bathroom and with a short, well-insulated primary run back to the heat pump. Every extra metre of pipe loses heat and slows reheat, and long dead legs to distant taps waste water while the customer waits for it to run hot.

  • Airing cupboard: often the best place, but measure the floor, the height and the door width, and check the floor can take the weight of a full cylinder.
  • Under the stairs or a box room: workable if the discharge pipe can reach a safe termination point.
  • Loft: avoid where possible. Weight, frost risk, service access and discharge routes all get harder.
  • Garage or outbuilding: only with good insulation, frost protection and an honest conversation about standing heat loss.
  • Kitchen or utility: fine if there is space, but check noise from valves and the customer’s view on losing a cupboard.

Show the customer the space you need with a tape measure on the survey. It avoids the most common late change of mind, which is discovering on fitting day that the new cylinder takes half the airing cupboard they use for towels.

Coil size and reheat time

A boiler heats a cylinder coil with water at a high flow temperature, so a small coil does the job. A heat pump runs at a lower flow temperature for efficiency, which means it needs a much larger coil surface to move the same heat into the store. Put a heat pump on a standard boiler cylinder and the coil becomes the bottleneck: the heat pump cannot dump its output, it cycles, and reheat drags on.

Compare cylinders on the coil surface area and the manufacturer's stated reheat time with a heat pump, not only on volume. Then match the coil to the heat pump's output across the flow temperatures you will actually run.

Example (fictional): a 200-litre cylinder heated from 10°C to 50°C needs about 9.3kWh (200 litres x 4.18kJ per litre per degree x 40 degrees, divided by 3,600). If the coil can take 6kW from the heat pump, that is roughly an hour and a half. If a small boiler coil limits transfer to 3kW, the same reheat takes over three hours, and the evening bath may run cold.

Ask for reheat time at the heat pump's real flow temperature. A figure quoted at boiler temperatures is no help to you or the customer.

Legionella: what HSE guidance actually says

HSE guidance is that hot water should be stored at 60°C or above and distributed so that it reaches 50°C at the outlets within one minute (55°C in healthcare premises), with cold water kept below 20°C where possible[2]. Many heat pump systems heat domestic hot water most efficiently below 60°C, which is why a periodic higher-temperature cycle is part of most designs.

HSE water temperature guidance for controlling legionellaOutlet target is 55°C in healthcare premises
HSE water temperature guidance for controlling legionellaColumn chart. Hot water stored at least: 60 °C; Hot water at outlets within 1 minute: 50 °C; Cold water kept below: 20 °C.0 °C20 °C40 °C60 °CHot water stored at least: 60 °C60 °CHot water stored at leastHot water at outlets within 1 minute: 50 °C50 °CHot water at outlets within 1minuteCold water kept below: 20 °C20 °CCold water kept belowHSE water temperature guidance for controlling legionellaColumn chart. Hot water stored at least: 60 °C; Hot water at outlets within 1 minute: 50 °C; Cold water kept below: 20 °C.Hot water stored at leastHot water stored at least: 60 °C60 °CHot water at outlets within 1 minuteHot water at outlets within 1 minute: 50 °C50 °CCold water kept belowCold water kept below: 20 °C20 °C

Source: Health and Safety Executive, 2026[2]

Show the data
ItemValue
Hot water stored at least60 °C
Hot water at outlets within 1 minute50 °C
Cold water kept below20 °C

For rented homes the landlord must assess the legionella risk, and HSE lists setting the cylinder to store water at 60°C among the simple control measures[4]. If you install for landlords or letting agents, agree in writing what the cylinder is set to and how the cycle runs, because their risk assessment will refer to it.

Setting up the pasteurisation cycle

  • Decide how the store reaches 60°C: a heat pump boost if the unit can reach it, or a timed immersion heater.
  • Set the frequency the manufacturer recommends and the risk assessment supports; many controllers default to once a week.
  • Schedule it overnight or at a cheaper tariff time, finishing before the morning peak so nobody is scalded and no hot water is wasted.
  • Fit a thermostatic mixing valve where the design or the household needs one, and check outlet temperatures at commissioning.
  • Check the immersion is wired, fused and switched on, and label the switch so it is not turned off to save money.
  • Record the settings, schedule and outlet temperatures on the commissioning record.

Unvented rules and paperwork

Most heat pump cylinders are unvented, so the installer needs the right unvented hot water competence and the work is notifiable. Installing or replacing a heating system can need Building Regulations approval in England[5], which in practice you handle by notifying through your competent person scheme. Check the discharge route, tundish position, expansion vessel and inlet pressure on survey, not on the day. Our guide to unvented cylinder installation has the full checklist.

Handover checklist

  1. Show the customer the cylinder temperature and the timer or app setting, and explain why it should not be lowered without asking you.
  2. Explain the pasteurisation cycle in one sentence and when it runs.
  3. Show the immersion switch and the label on it.
  4. Run a bath or two showers back to back with the customer, so they see what the store delivers.
  5. Leave the reheat time in writing, with the time it takes to recover after a full bath.
  6. Book the first service and add the cylinder and valves to the service checklist; see heat pump aftercare.

If the customer worries about stored hot water after years of a combi, the honest framing is in our guide to heat pump objections: a properly sized store runs out less often than people fear, and the cylinder can be topped up by an immersion or, where they have panels, a solar diverter.

Frequently asked questions

What size cylinder do I need with a heat pump?

Size from the number of people, how many baths and showers happen at the busiest time, and the storage temperature, then confirm with the manufacturer's sizing tool. A one-for-one swap of the old tank is often too small.

Can I use my existing cylinder with a heat pump?

Usually not well. A standard boiler cylinder has a small coil designed for high flow temperatures, so a heat pump cannot transfer heat fast enough and reheat times stretch.

How hot should a heat pump cylinder be for legionella?

HSE guidance is to store hot water at 60°C or above and reach 50°C at outlets within a minute[2]. Systems that store lower usually run a periodic cycle to 60°C.

Do landlords need a legionella certificate?

No. HSE says landlords must assess the risk, but health and safety law does not require a legionella test certificate, and testing is not usually needed in domestic systems[4].

References

  1. Ministry of Housing, Communities and Local Government (GOV.UK) (2024). English Housing Survey 2024 to 2025: Chapter 2, energy efficiency (opens in a new tab) ↑

  2. Health and Safety Executive (2026). Legionnaires’ disease: hot and cold water systems (opens in a new tab) ↑

  3. Department for Energy Security and Net Zero (2026). Boiler Upgrade Scheme (BUS) monthly statistics: England and Wales, September 2026 (opens in a new tab) ↑

  4. Health and Safety Executive (2026). Legionella and landlords’ responsibilities (opens in a new tab) ↑

  5. GOV.UK (2026). Building regulations approval (opens in a new tab) ↑