Key takeaways
- HSE control temperatures: store hot water at 60°C or above, reach at least 50°C at outlets within a minute, and keep cold water below 20°C[1].
- Summer raises the risk in two ways: cold water warms in pipes and tanks, and holiday homes, empty rentals and quiet buildings let water stagnate.
- Infrequently used outlets should be flushed weekly[2]; for long vacancies, a flushing regime or draining the system is advised[3].
- Landlords have a duty to assess legionella risk, though most can do it themselves without an in-depth assessment[3].
- Combination boilers store no hot water and now heat most homes[4]; systems with cylinders and tanks need more attention.
Why summer is a legionella season
Legionella bacteria live in water systems and cause disease when contaminated water is breathed in as fine droplets, most often from showers and spray taps. The risk is controlled mainly by temperature and by keeping water moving. Summer works against both.
Cold water pipes and storage tanks warm up in hot weather, especially in lofts and plant rooms. At the same time, many systems sit unused: holiday lets between bookings, rentals between tenants, second homes, schools and offices over the summer break, and family homes left empty during a fortnight away. With heating off, household gas use in July to September 2025 was less than a fifth of the January to March 2026 level[5], and some households turn cylinder temperatures down to save energy.
The temperatures that matter
The Health and Safety Executive sets out the core control temperatures. Hot water should be stored at 60°C or above and distributed so that it reaches 50°C at outlets within one minute, or 55°C in healthcare premises. Cold water should be kept below 20°C where possible[1].
Source: Health and Safety Executive, 2026[1]
Show the data
| Control point | Value |
|---|---|
| Cold water: keep below | 20 °C |
| Hot at outlets within 1 minute | 50 °C |
| Hot at outlets, healthcare | 55 °C |
| Hot water storage: at least | 60 °C |
These figures give plumbers simple checks on any visit: run the hot tap and time how long it takes to reach 50°C, check the cylinder thermostat setting, and feel or measure the cold water after a short run. A cold tap that runs warm in July is a sign of a system that needs attention.
Which properties need attention
- Holiday lets and second homes left empty for weeks.
- Rented homes between tenants.
- Homes where an older person has been in hospital or away.
- Schools, nurseries and offices over the summer holidays.
- Sports pavilions, village halls and seasonal businesses.
- Homes with cold water storage tanks in hot lofts.
- Systems with dead legs left after alterations, such as a removed basin or outside tap.
Workplaces and larger buildings fall under the HSE's approved code of practice and technical guidance, which require a proper risk assessment by a competent person. For domestic customers and small landlords, the advice below is the practical part plumbers are most often asked about.
Landlords' duty
Landlords have a duty to assess the risk from exposure to legionella to ensure the safety of their tenants. The HSE says this does not require an in-depth, detailed assessment, most landlords can do it themselves, and records are not a legal requirement for them[3]. Outlets should be used at least weekly to keep water moving, and for longer vacancies the HSE recommends a suitable flushing regime or measures such as draining the system so water does not stagnate[3].
Plumbers can help landlords meet that duty by flagging risks on visits: stored hot water below temperature, cold water tanks without lids, dead legs and showers in rooms that are rarely used.
Flushing routine for returning occupants
When customers return to a home that has been empty for a week or more in warm weather, give them a simple routine. For properties empty for much longer, or where anyone in the household is at higher risk, offer to do it for them.
Heat the hot water first
If there is a cylinder, let it reach its normal storage temperature before running hot taps.
Run the cold taps
Run each cold tap for a few minutes until the water feels noticeably colder than when it started.
Run the hot taps
Run each hot tap until the water is hot and then for a little longer.
Showers last and gently
Run showers with the head in the tray or bath, or removed, to reduce spray. Close the door and leave the room while it runs if possible.
Flush toilets
Flush every toilet, with the lid down.
Clean showerheads
Remove, clean and descale showerheads and hoses; the HSE advises regular cleaning and disinfection of showerheads[3].
The aim is to replace water that has been sitting in the system with fresh mains water and hot water at full temperature, while keeping spray to a minimum.
Infrequently used outlets
Guest bathrooms, utility room taps and outside showers can be a risk even in occupied homes. The HSE advises a programme of regular, weekly flushing for infrequently used outlets, flushing to drain without releasing aerosols, and removing dead ends or regularly flushing dead legs[2]. Suggest customers add a weekly run of any little-used tap or shower to their routine, or consider removing outlets nobody uses.
Combi boilers and stored hot water
The type of system changes the risk. Combination boilers heat water on demand and store none, and condensing combis were in 63% of homes in England in 2024; condensing regular or system boilers, usually paired with a cylinder, were in 19%[4]. Homes with hot water cylinders, cold water storage tanks or both need more care, particularly when the cylinder is turned down or the home is empty.
- Check cylinder thermostats are set to store at 60°C or above[1].
- Explain why turning the cylinder down to save energy in summer is a false economy.
- Check that timers allow the cylinder to reach temperature regularly.
- Make sure cold water storage tanks have close-fitting lids and are insulated.
- For heat pump and solar cylinders, check any scheduled high-temperature cycle is working.
Bathroom refits and dead legs
Alterations are a common source of stagnant water. When a basin, bidet or outside tap is removed, the pipe that fed it is often capped close to the outlet rather than at the branch, leaving a dead leg where water never moves. Remove redundant pipework back to the supply on every refit, and note any you find on other jobs. It is cheap to fix at the time and hard to justify leaving.
What to check on any summer visit
You do not need a separate visit to spot legionella risks. On services, repairs and installs through the summer, add a few quick checks to the routine and note anything you find on the job sheet.
- Cylinder thermostat setting and the actual stored temperature where you can measure it.
- Time for the hot tap nearest the cylinder to reach 50°C.
- Cold water temperature after a short run, especially from tanks in lofts.
- Condition of any cold water storage tank: lid, insulation, debris.
- Showers and outlets that the customer says are rarely used.
- Dead legs or capped pipework left from earlier alterations.
Explain any concern in plain terms and put it in writing. Most customers have never heard of the temperature rules, and a short explanation of why the cylinder should not be turned down is often enough.
What plumbers should not do
Be clear about the limits of a domestic visit. A plumber checking a holiday cottage is not carrying out a formal legionella risk assessment for a workplace, and should not call their checks one. For schools, offices, care homes and other premises covered by the HSE's workplace guidance, point the client to a competent risk assessor if they do not already have one, and offer to carry out the remedial plumbing work that assessment identifies. Avoid chemical disinfection of domestic systems unless you are trained to do it and the circumstances require it.
Example: a holiday cottage changeover
Example (fictional): the owner of a holiday cottage in Cornwall asks a local plumber for help after the property sits empty for three weeks in a hot June. The cottage has a vented cylinder and a cold water tank in the loft. The plumber finds the cylinder thermostat set low, resets it, checks the tank lid and insulation, and runs every outlet following the routine above, showers last. He removes a dead leg left from an old outside tap. He leaves the owner a one-page changeover routine for cleaners to follow when the property has been empty for more than a week, including weekly flushing of the rarely used second shower.
Related reading
For empty homes in winter, see winterising empty properties in the same seasonal series. Drought brings its own questions, covered in hosepipe bans and drought. For planning summer work around staff leave, read school holidays and staff leave planning.
Frequently asked questions
What temperature should a hot water cylinder be set to?
The HSE says hot water should be stored at 60°C or above and reach at least 50°C at outlets within one minute[1].
How often should a little-used shower be run?
Weekly. The HSE advises a programme of regular weekly flushing for infrequently used outlets[2].
Do landlords need a professional legionella risk assessment?
Not usually for ordinary homes. The HSE says landlords have a duty to assess the risk, but it does not need to be in-depth and most landlords can do it themselves[3].
Are combi boilers a legionella risk?
Lower than systems with stored hot water, because a combi stores none. Cold water pipes and little-used outlets still need water moving through them.
References
Health and Safety Executive (2026). Legionnaires' disease: hot and cold water systems (opens in a new tab) ↑
Health and Safety Executive (2026). Legionnaires' disease: things to consider (opens in a new tab) ↑
Health and Safety Executive (2026). Legionnaires' disease: landlords' responsibilities (opens in a new tab) ↑
Ministry of Housing, Communities and Local Government (GOV.UK) (2024). English Housing Survey 2024 to 2025: Chapter 2, energy efficiency (opens in a new tab) ↑
Department for Energy Security and Net Zero (2026). Energy Trends: UK gas, ET 4.1 natural gas supply and consumption (quarterly), September 2026 (opens in a new tab) ↑