Suspected carbon monoxide calls: what an engineer should do

A safe sequence for suspected carbon monoxide calls: phone advice, arrival checks, isolating appliances, unsafe situations and reporting to HSE.

Ava research teamPublished 7 min read

On this page
  1. Why carbon monoxide calls need their own procedure
  2. On the phone, before anyone sets off
  3. Arrival: a safe sequence
  4. Shared flues, neighbours and other sources
  5. Applying the unsafe situations procedure
  6. What must be reported, and by whom
  7. Documenting the visit
  8. After the visit
  9. Example: an alarm in a top-floor flat
  10. Frequently asked questions
  11. References

Key takeaways

  • Carbon monoxide poisoning was behind 92 of the 129 flammable gas incidents causing injury reported to HSE in 2024/25[1].
  • On the phone, give the NHS advice first: stop using the suspect appliance, get outside and get medical advice[2].
  • Wear a personal CO monitor before you enter and treat every alarm as real until your readings prove otherwise.
  • A dangerous gas fitting caused by its installation or servicing must be reported to HSE within 14 days[3].

Why carbon monoxide calls need their own procedure

A carbon monoxide call is not a breakdown with a nervous customer. The caller may already be unwell, the danger is invisible, and the source may not be the appliance they mention. The NHS lists gas boilers, gas cookers and gas or paraffin heaters among household appliances that can produce carbon monoxide when badly installed, faulty or poorly maintained[2]. A firm that takes emergency calls needs a fixed sequence that every engineer and call handler follows the same way.

The numbers have been rising. HSE's RIDDOR data shows carbon monoxide poisoning incidents in Great Britain rose from 51 in 2021/22 to 92 in 2024/25 (provisional), and non-fatal CO injuries reached 133 that year[1]. Some of the increase may reflect reporting, but either way every engineer should expect to meet these calls.

Carbon monoxide poisoning incidents reported under RIDDOR, Great BritainFlammable gas incidents resulting in injury; 2024/25 provisional; 2020/21 and 2021/22 may be affected by the pandemic
Carbon monoxide poisoning incidents reported under RIDDOR, Great BritainLine chart. 2020/21: 67; 2021/22: 51; 2022/23: 63; 2023/24: 84; 2024/25: 92.4060801002020/212021/222022/232023/242024/252020/21: 672021/22: 512022/23: 632023/24: 842024/25: 929267Carbon monoxide poisoning incidents reported under RIDDOR, Great BritainLine chart. 2020/21: 67; 2021/22: 51; 2022/23: 63; 2023/24: 84; 2024/25: 92.4060801002020/212022/232024/252020/21: 672021/22: 512022/23: 632023/24: 842024/25: 929267

Source: Health and Safety Executive, 2025[1]

Show the data
PeriodValue
2020/2167
2021/2251
2022/2363
2023/2484
2024/2592

Detection is still patchy. Only 62% of dwellings in England had a carbon monoxide alarm in 2024[4], so many incidents are first noticed through symptoms rather than an alarm.

On the phone, before anyone sets off

The person answering the phone sets the tone. Their job is to protect the caller first and book an engineer second. Keep the advice short and from approved sources; do not diagnose.

  1. Ask whether anyone feels unwell: headache, dizziness, nausea, weakness, confusion or breathlessness.
  2. Give the NHS advice: stop using the appliance you think might be making carbon monoxide, go outside and get medical advice as soon as possible, and do not go back in until told it is safe[2].
  3. If anyone is struggling to breathe, confused or unconscious, tell the caller to ring 999 now.
  4. If they can smell gas, give the National Gas Helpline number, 0800 111 999, which the NHS also lists[2].
  5. Take the address, a contact number for outside the property, and the appliances in the home.
  6. Tell them who is coming and roughly when, and ask them to keep the phone with them.

Script: "Please turn off the boiler if you can do it safely, then go outside with everyone in the house. If anyone has a headache, feels sick or dizzy, call NHS 111 now, or 999 if someone is very unwell. We'll send an engineer. Please don't go back inside until we've checked it."

Arrival: a safe sequence

  1. Protect yourself

    Switch on your personal CO monitor before entering. If it alarms at the door, ventilate from outside where possible and do not stay in the property.

  2. Check the people

    Ask again about symptoms. If anyone is unwell and has not had medical advice, that comes before any appliance work.

  3. Ventilate and isolate

    Open windows and doors, turn off suspected appliances and isolate gas at the meter if you cannot identify the source quickly.

  4. List every combustion source

    Boiler, cooker, gas fire, water heater, open fire, wood burner, oil appliances, generators, cars in an attached garage. The source is not always gas.

  5. Inspect the alarm

    Note make, age, location and whether it meets EN 50291-1, which all CO alarms in the UK must meet[5]. Record what it displays or logged.

  6. Test appliances and flues

    Carry out flue flow, spillage and combustion checks to your training and the manufacturer's instructions. Inspect flue routes, terminals and voids, including any flue running through other rooms.

  7. Classify and act

    Apply the unsafe situations procedure to anything you find, issue notices and labels, and explain the outcome to the customer in plain words.

Shared flues, neighbours and other sources

Flats and terraces add complications. A flue may pass through a neighbour's property, or fumes from next door may be entering through a shared chimney or a gap in a party wall. If your readings show carbon monoxide but every appliance in the property tests clean, widen the search: ask about neighbouring appliances, check chimneys shared with adjoining homes and consider whether the gas emergency service or a solid fuel specialist should be involved.

Do not dismiss an alarm as faulty without evidence. Alarms do reach end of life and can be affected by some other gases, but the correct response is to establish why it sounded. If you replace an old alarm, leave the old one with the customer or note its details, so the history is not lost.

Applying the unsafe situations procedure

Where you find an appliance that is immediately dangerous, the industry procedure is to disconnect it from the gas supply with the customer's permission, attach a warning label and give a written warning notice. Where an appliance is at risk, turn it off with permission and advise that it should not be used until repaired. Explain the reason in everyday language: "this boiler is putting carbon monoxide into the room, and that can kill" is clearer than a category code.

If the customer refuses permission to make an immediately dangerous appliance safe, do not argue on the doorstep and do not leave without acting. Contact the gas emergency service, which can attend and make the installation safe. When notified of a gas escape, the gas conveyor must attend as soon as reasonably practicable and stop the escape within 12 hours[6]. Record the refusal, the time you called and who you spoke to.

What must be reported, and by whom

Two parts of RIDDOR regulation 11 apply. Gas conveyors and certain LPG suppliers who learn of a death, loss of consciousness or hospital visit caused by an injury arising from gas must notify HSE without delay and send a report within 14 days[3]. Separately, a Gas Safe registered business that has enough information to decide that the design, construction, installation, modification or servicing of a gas fitting is or has been likely to cause death, loss of consciousness or hospital treatment, through leakage, incomplete combustion or inadequate removal of combustion products, must report it to HSE within 14 days[3].

In practice, the engineer's duty usually turns on the cause. A boiler producing carbon monoxide because its flue was installed wrongly is reportable; one that has simply worn out may not be. If you are unsure, record your evidence on the night and get a second opinion before the deadline.

Documenting the visit

  • Times of call, advice given on the phone and arrival.
  • Symptoms reported and whether medical help was advised or sought.
  • Your personal monitor readings on entry and during the visit.
  • Every combustion appliance found, test results and flue observations.
  • Alarm details and condition.
  • Unsafe situation classification, notices issued, customer response, and any escalation or report.

After the visit

Ring the customer the next day. Ask how everyone feels, whether they followed up on medical advice, and whether the alarm has stayed quiet. If an appliance was disconnected, confirm the repair or replacement plan and when you can return. For rented homes, check the landlord has received the warning notice and is acting on it. A short follow-up call is good care, and it often reveals a second problem, such as a neighbour's appliance, that nobody mentioned on the night.

Example: an alarm in a top-floor flat

Example: a tenant rings at 8pm because the CO alarm in her hall keeps sounding. She has a headache. The call handler tells her to turn off the boiler, leave the flat and ring NHS 111, and books the on-call engineer. On arrival the engineer's monitor reads low levels inside the flat. The boiler combustion reading is poor and the flue joint in the loft void has separated.

Example, continued: the engineer classes the boiler as immediately dangerous, disconnects it with the tenant's agreement, labels it and issues a warning notice. Because the fault arises from how the flue was installed, the firm reports it to HSE within the 14-day period and sends the landlord a copy of the notice and job sheet the same evening.

Frequently asked questions

What should I do if my carbon monoxide alarm goes off?

Stop using appliances you think may be producing carbon monoxide, go outside and get medical advice[2]. Ring 999 if anyone is seriously unwell, and get a Gas Safe registered engineer to check your appliances.

What number do I call if I smell gas?

The National Gas Helpline on 0800 111 999, open 24 hours[2].

Will a gas engineer turn off my boiler if it is producing carbon monoxide?

If it is immediately dangerous, the engineer will ask permission to disconnect it, label it and give you a warning notice. If you refuse, they can contact the gas emergency service.

Do gas engineers report carbon monoxide incidents to HSE?

A registered business must report dangerous gas fittings where the danger arises from design, installation, modification or servicing, within 14 days[3]. Gas conveyors report incidents involving death or hospital treatment.

References

  1. Health and Safety Executive (2025). RIDGAS: Gas-related incidents reported in Great Britain (Tables 1 and 2) (opens in a new tab) ↑

  2. NHS (2026). Carbon monoxide poisoning (opens in a new tab) ↑

  3. legislation.gov.uk (The National Archives) (2013). The Reporting of Injuries, Diseases and Dangerous Occurrences Regulations 2013, regulation 11 (opens in a new tab) ↑

  4. Ministry of Housing, Communities and Local Government (GOV.UK) (2024). English Housing Survey 2024 to 2025: Chapter 1, housing quality (opens in a new tab) ↑

  5. Heating and Hotwater Industry Council (HHIC) (2025). A guide to carbon monoxide (CO) alarm legislation for heating engineers (opens in a new tab) ↑

  6. legislation.gov.uk (The National Archives) (1996). The Gas Safety (Management) Regulations 1996, regulation 7 (opens in a new tab) ↑